USFA COFFEE BREAK TRAINING: FIRE PROTECTION SERIES

 Automatic Sprinklers: Calculating Pressure Changes Due to Temperature

No. FP-2013-REV18 April 30, 2013

Learning Objective: The student shall be able to calculate air pressure changes in a sprinkler system that result from temperature fluctuations.

During a dry pipe sprinkler system pneumatic test, a change in ambient temperature may cause the air in the system to expand or contract, resulting in what may appear to be an inconsistent pressure reading on the test gauge. 

To account for changes in air temperature, the inspector can use the following formula to assure the minimum requirement of 40 pounds per square inch (2.8 bar) has been sustained.

P1(T2/T1) = P2 Where, P1 = gauge pressure at the start of the test (pounds per square inch gauge)
P2 = gauge pressure at the end of the test (psig)
T1 = ambient temperature at the start of the test
T2 = ambient temperature at the end of the test

It is important to note that for the formula to work, the temperatures need to be converted to the Rankine scale by adding 460 to the recorded temperature in Fahrenheit (273 for Celsius).

Here is an example in American Standard units where the temperature increases from 43 F to 78 F during the 24-hour test when the sprinkler system is pressurized to 40 psig and it is assumed that the system is at sea level. If there are no leaks in the system, the formula will provide the gauge pressure that would be expected at the end of the test.

Given, P1 = 40 psig

T1 = 43 F + 460 = 503 R

T2 = 78 F + 460 = 538 R

40(538/503) = 42.8 psig

Conversely, if the temperature dropped by the same amount during the test, the results would appear as:

Given, P1 = 40 psig

T1 = 78 F + 460 = 538 R

T2 = 43 F + 460 = 503 R

40(503/538) = 37.4 psig

In the second example, even though the gauge pressure reads less than the beginning 40 psig, the inspector can conclude that the system has passed the pressure test and the lower gauge reading is due to temperature fluctuations.

This air pressure gauge dropped below the 40 pounds per square inch (2.8 bar) threshold during a pneumatic test. The inspector must determine if the loss is a result of a leak or ambient temperature fluctuations.
Original Source .pdf: http://www.usfa.fema.gov/downloads/pdf/coffee-break/cb_fp_2013_18.pdf
Eligible for Continuing Education Units (CEUs)
at www.usfa.fema.gov/nfaonline
For archived downloads, go to: 
www.usfa.fema.gov/nfa/coffee-break/

No comments:

Post a Comment

CAL FIRE NEWS LOVES COMMENTS...
- Due to rampant abuse, we are no longer posting anonymous comments. Please use your real OpenID, Google, Yahoo, AIM, Twitter, Flickr name.


Twitter Buttons

****REMINDER**** Every fire has the ability to be catastrophic. The wildland fire management environment has profoundly changed. Growing numbers of communities, across the nation, are experiencing longer fire seasons; more frequent, bigger, and more severe, fires are a real threat. Be careful with all campfires and equipment.

"I am a firm believer in the people. If given the truth, they can be depended upon to meet any national crisis. The great point is to bring them the real facts, and beer." --Abraham Lincoln

View blog top tags
---------------------
CLICK HERE TO GO BACK TO TOP OF CALIFORNIA FIRE NEWS HOME PAGE

Subscribe via email to California Fire News - Keep track of Cal Fire News

Enter your email address:

Delivered by FeedBurner