Coffee Break Training (Fire Protection): Hazardous Materials - Aboveground Flammable and Combustible Liquid Tank Emergency Venting - Part 4: Wetted Area

 Learning Objective: The student shall be able to explain and calculate the wetted area of an aboveground flammable and combustible liquid tank. 

Atmospheric, aboveground flammable and combustible liquid storage tanks that rely solely on pressure-relieving devices for emergency venting must have normal and emergency vents capable of preventing the rupture of the shell or bottom of a vertical tank or the shell or ends of a horizontal tank.  An aboveground tank is one that is installed above grade, at grade or below grade without backfill, leaving its exterior surfaces exposed to the atmosphere.

 The combined air flow capacity of the normal and emergency vents is measured in cubic feet per hour (m3/hour) of free flowing air through the venting assemblies. The minimum air flow is derived from the “wetted area” of a storage tank, which is the surface area of the tank that normally is in contact with the liquid contents. Once the wetted area is established, minimum air flow volumes are found in a table in National Fire Protection Association 30, Flammable and Combustible Liquids Code.

 To calculate the wetted area, NFPA 30 measures it as a portion of the entire tank external surface area that is exposed to the atmosphere. An adjustment is based on the shape of the tank as follows: 
Aboveground Tank Type / Amount of Exposed Area for Calculation
 *Aboveground tanks operating at a gauge pressure of more than 1 psi (6.9 kPa) employ different guidelines.

For example, the illustrated tank is less than 30 feet (9 m) tall, so its entire surface area is included in the wetted area calculation. Assuming that the tank is 20 feet (6.1 m) in diameter and 28 feet (8.5 m) tall, the formula to determine its wetted area is:
Wetted area = (πd)H
Where,
π = 3.14
d = tank diameter
H = tank height

Next week’s Coffee Break Training will provide calculation examples of other tank configurations. Subsequent Coffee Break Training items will explain ventilation requirements derived from the wetted area calculation. For additional information, refer to NFPA 30, Chapter 22.
Original NFPA .pdf link: http://www.usfa.fema.gov/downloads/pdf/coffee-break/cb_fp_2013_4.pdf

No comments:

Post a Comment

CAL FIRE NEWS LOVES COMMENTS...
- Due to rampant abuse, we are no longer posting anonymous comments. Please use your real OpenID, Google, Yahoo, AIM, Twitter, Flickr name.


Twitter Buttons

****REMINDER**** Every fire has the ability to be catastrophic. The wildland fire management environment has profoundly changed. Growing numbers of communities, across the nation, are experiencing longer fire seasons; more frequent, bigger, and more severe, fires are a real threat. Be careful with all campfires and equipment.

"I am a firm believer in the people. If given the truth, they can be depended upon to meet any national crisis. The great point is to bring them the real facts, and beer." --Abraham Lincoln

View blog top tags
---------------------
CLICK HERE TO GO BACK TO TOP OF CALIFORNIA FIRE NEWS HOME PAGE

Subscribe via email to California Fire News - Keep track of Cal Fire News

Enter your email address:

Delivered by FeedBurner